Door Access Control Quick Start Guide
Click here for related documentation.
Panel Wiring Diagram
Panel Wiring Legend
Item | Description | Ordering Information |
---|---|---|
A |
Access Control Reader |
Inex P/N: IZACR-QPR50 |
B |
Reader-to-Panel Cable*: 4-conductor copper wires; use 22 AWG for up to 250 ft (76 m), or 18 AWG for 250-500 ft (152 m) |
Supplied by integrator |
C |
Four-Door Access Control Panel |
Inex P/N: IZACP-4D |
D |
Network Switch |
Supplied by integrator |
E |
Cat6 LAN Cable**; Max. Length 330 ft (100 m) |
Supplied by integrator |
F |
Power Supply for Access Panel: 12 VDC, 75W; DIN rail |
Inex P/N: IZPWR75-12-MWL-DIN |
G |
Power Supply for Locks: 12/24 VDC (depends on lock type), 120W; DIN rail |
|
H |
Electric Lock |
Supplied by integrator |
I |
Panel-to-Lock Cable (see AWG tables below) |
Supplied by integrator |
J |
Sensor (to determine if door is opened or closed) |
Supplied by integrator |
K |
Exit Button |
Supplied by integrator |
* Shielded cable of excellent quality in a noise free environment
** With Wi-Fi option, cable is not needed
Emergency Open/Fire Wiring Diagram
Fire Wiring Legend
Item | Description | Ordering Information |
---|---|---|
L |
Emergency Open/Fire Button (opens all doors) |
Supplied by integrator |
M |
Fire Alarm |
Supplied by integrator |
The following recommended wire gauge selection tables for the panel-to-lock (or alarm) cables are based on the 2008 National Electrical Code (2008 NEC). The maximum wire gauge that fits in the access control panel connectors is 12 AWG.
AWG Wire Gauge Selections - Electric Strike Current at 12 VDC
Electric Strike Current → Total one way length of wire run (ft/m) |
1/4A | 1/2A | 3/4A | 1A | 1-1/4A | 1-1/2A | 2A |
---|---|---|---|---|---|---|---|
100 (30 m) |
18 |
16 |
14 |
12 |
12 |
--- |
--- |
150 (46 m) |
16 |
14 |
12 |
--- |
--- |
--- |
--- |
200 (61 m) |
16 |
12 |
--- |
--- |
--- |
--- |
--- |
250 (76 m) |
14 |
12 |
--- |
--- |
--- |
--- |
--- |
300 (91 m) |
14 |
--- |
--- |
--- |
--- |
--- |
--- |
400 (122 m) |
12 |
--- |
--- |
--- |
--- |
--- |
--- |
500 (152 m) |
12 |
--- |
--- |
--- |
--- |
--- |
--- |
AWG Wire Gauge Selections - Electric Strike Current at 24 VDC
Electric Strike Current → Total one way length of wire run (ft/m) |
1/4A | 1/2A | 3/4A | 1A | 1-1/4A | 1-1/2A | 2A |
---|---|---|---|---|---|---|---|
100 (30 m) |
20 |
18 |
16 |
16 |
14 |
14 |
12 |
150 (46 m) |
20 |
16 |
14 |
14 |
12 |
12 |
--- |
200 (61 m) |
18 |
16 |
14 |
12 |
12 |
--- |
--- |
250 (76 m) |
18 |
14 |
12 |
12 |
--- |
--- |
--- |
300 (91 m) |
16 |
14 |
12 |
--- |
--- |
--- |
--- |
400 (122 m) |
16 |
12 |
--- |
--- |
--- |
--- |
--- |
500 (152 m) |
14 |
12 |
--- |
--- |
--- |
--- |
--- |
750 (229 m) |
12 |
--- |
--- |
--- |
--- |
--- |
--- |
1000 (305 m) |
12 |
--- |
--- |
--- |
--- |
--- |
--- |
© Inex Technologies, LLC - All rights reserved. Specifications are subject to change without notice. All third-party trademarks are the property of their respective owners.
Doc. No. SLN-DOOR-AC-TECH-001